A proper service inspects and analyses before it cleans, covers flue integrity, ventilation, gas rate and safety devices, and produces a written record with combustion readings. A ten-minute visit and a sticker is not one.
Inspection before maintenance
The sequence matters. What the initial checks reveal determines what the rest of the visit involves – and cleaning before measuring destroys the evidence of how the appliance has actually been running.
- Check the surroundings before touching the applianceFlue route and terminal position, ventilation provision, clearances, compartment condition, and whether anything has changed since last time – a new extractor, a blocked airbrick, a boxed-in flue.
- Run it and observeIgnition sequence, flame picture where visible, controls, any unusual noise, and how it behaves through a cycle.
- Combustion analysisAn electronic flue gas analyser measures the ratio of carbon monoxide to carbon dioxide. This is the single most important output of the visit – an objective measure of whether the appliance is burning correctly.
- Gas rate and operating pressureChecked against the appliance data plate. An appliance running outside its rated gas rate is not set up correctly, whatever else looks fine.
- Flue integrityAlong its accessible length, including inspection hatches where they exist. A flue that has separated in a loft void discharges combustion products into the building.
- Safety device operationFlame supervision, overheat protection, and any other protective device the appliance relies on.
- Then clean and adjustCondensate trap cleaned, heat exchanger and burner cleaned to the manufacturer’s specification, seals checked and replaced as needed, electrodes inspected.
- Recommission and recordAnalyser reading taken again after cleaning, and the findings written down.
The condensate trap, which gets skipped
Worth its own mention because it causes several apparently unrelated faults.
A condensing boiler’s condensate trap collects acidic condensate before it drains. Over a year it accumulates a sludge of combustion residue. When that trap partially blocks, the boiler cannot drain properly, and the resulting fault codes are frequently not obviously condensate-related – ignition lockouts, fan or air pressure faults, and flame loss during operation all appear.
Cleaning the trap is a standard part of a service and it is one of the more commonly omitted steps, because it is dirty and fiddly. If your boiler has a history of intermittent lockouts and the trap has never been cleaned, that is worth mentioning.
The readings, and what they mean
An analyser prints a ticket. Ask for it and keep it, because the year-on-year trend is more informative than any single visit.
| Reading | What it is | What a poor figure means |
|---|---|---|
| CO/CO2 ratio | Carbon monoxide relative to carbon dioxide in the flue gases | The key combustion measure. Industry thresholds define where an appliance becomes unsafe |
| CO in ppm | Absolute carbon monoxide concentration | Safety measure. High CO with a high ratio means the burner needs work, not adjustment |
| Flue gas temperature | How hot the exhaust leaves | A figure rising year on year means the heat exchanger is fouling |
| Gas rate | Fuel consumed against the data plate figure | Under-rating means the appliance is not delivering its output; over-rating is unsafe |
| Working and standing gas pressure | At the appliance | Low working pressure under load points at supply or pipe sizing |
Not afterwards. Saying at the point of booking that you would like the combustion readings tells you immediately what kind of visit you are getting, and any engineer doing the job properly will be pleased to provide them.
Service versus safety check
These are routinely conflated and they are different pieces of work.
| Gas safety check | Service | |
|---|---|---|
| Purpose | Is it safe? | Is it safe, clean, correctly set and maintained? |
| Legal status | Annual legal duty for landlords | Not a legal duty for owner-occupiers |
| Warranty | Does not satisfy the manufacturer’s condition | Does, when recorded |
| Includes cleaning | No | Yes |
| Includes the condensate trap | No | Yes |
| Produces | A gas safety record | A service record, plus a safety assessment |
| Typical duration | Shorter | Longer |
A landlord’s legal duty is the check. A manufacturer’s warranty condition is the service. Most landlords want both, and they are commonly done in one visit – see landlord gas safety certificates.
How to tell it did not happen
- It took a few minutes. A proper service cannot.
- You were given no readings, and no ticket from an analyser.
- Nothing was opened up. A service produces waste – old seals, soot, condensate trap contents.
- The engineer never looked at the flue, or at any inspection hatches.
- Ventilation was not mentioned, and no airbricks were checked.
- The benchmark or service record was not completed, or was signed without entries.
- Nothing was said about the system – pressure, filter, inhibitor.
- You received a sticker and an invoice and nothing else.
None of these individually proves bad faith. Together they describe a visit that did not do what a service does, and it is entirely reasonable to ask about them.
What else should get mentioned
A service visit is the natural moment to look at the things that will cause the next call-out. A good engineer covers these without being asked:
- System pressure and whether it has needed topping up – which if it has, means a leak.
- The magnetic filter, emptied and what came out of it reported – see magnetic system filters.
- Inhibitor level, tested rather than assumed.
- The condensate route, particularly any external section, before winter rather than during it.
- Controls – whether they are set sensibly, and whether the flow temperature could come down.
- Any CO alarm in the property, present and in date.
- Radiator performance, if anything is obviously cold.
Those are five minutes of attention that prevent a disproportionate number of winter call-outs.
Booking a service? Ask for the combustion readings when you book. It tells you immediately what kind of visit you are getting.
Questions we get asked about this
How long should a gas boiler service take?
Long enough to run the appliance, take combustion readings, check the flue, ventilation and gas rate, clean the condensate trap and the burner, and record the findings. A visit measured in a few minutes has not done those.
Is an annual service a legal requirement?
For landlords, the annual safety check is a legal duty. For owner-occupiers there is no legal requirement, but every manufacturer makes the warranty conditional on an annual service by a competent person.
What is the difference between a service and a safety check?
The check establishes safety and produces the legal record. The service includes that plus the manufacturer’s cleaning and maintenance. The landlord duty is the check; the warranty condition is the service.
Should I be given readings?
Yes. A combustion analyser prints a ticket and it is the objective evidence the appliance was left burning correctly. Keep them – the year-on-year trend tells you how the boiler is ageing.
My boiler works fine. Do I need it serviced?
Yes, and the safety argument is why. An appliance can burn incorrectly and produce carbon monoxide while heating the house perfectly normally. There is no symptom you would notice, which is precisely the point.
When is the best time to book?
Spring or summer. Out of season the diary is open, and anything needing a part can be dealt with in weeks rather than during a cold snap.
You might also need
- Boiler fault codes: what they actually tell you
- Boiler Plus: what has to be fitted alongside a new boiler
- Boiler pressure: why it drops, why it climbs, and what to do
- Boiler warranties, and the things that quietly void them
- Combi, system or regular: choosing the right boiler type
- Flue positions, and why the location decides the boiler