Burst pipe or no heating? We take emergency call-outs across Norfolk — 07506 070316

Commercial & larger works →
Lex Plumbing Call 07506 070316
Oil
Boilers
Tanks and supply
Gas
Boilers
Safety and appliances
Cooling
Air conditioning
Heat pumps
Hot water
Cylinders
Problems and parts
Heating
Systems
Controls and parts
Plumbing
Emergencies
Everyday plumbing
Mains and waste
Bathrooms
Installations
Fittings
GuidesAreasContact
Gas

Gas supply and pipe sizing: the check most quotes skip

Why undersized gas pipework starves appliances, how the check is done, and what to do when the meter is the constraint.

Short answer

Gas leaves the meter at a regulated pressure, and every metre of pipe and every fitting causes a pressure drop. There is a maximum permissible drop to the appliance, and staying within it is a calculation – one that is routinely skipped when a higher-output boiler replaces an older one.

The physics, briefly

Gas is supplied at the meter at a regulated pressure. As it flows through pipework, friction causes a pressure drop, and that drop increases with:

  • Flow rate – more appliances running simultaneously means more gas moving.
  • Pipe length – every metre adds resistance.
  • Number and type of fittings – each elbow, tee and valve counts.
  • Reduced diameter – and this one is dramatic. Pressure drop rises very sharply as bore reduces, so going down one pipe size increases the drop by far more than proportionally.

There is a maximum permissible pressure drop between the meter and any appliance, and the design job is to size the pipework so that the drop stays within it with every appliance running at once.

The symptom is not a failure

This is why it gets missed. An appliance on an undersized supply still lights and still works – it simply cannot achieve its rated output when other things are running. The boiler seems weak, locks out under load in cold weather, or the hob and the boiler interfere with each other, and none of it looks like a pipework problem.

Why replacements are where it goes wrong

The single most common scenario: an older, lower-output boiler is replaced with a modern one of higher output, on the existing pipework.

The old appliance was within the capacity of that pipe. The new one is not. Nothing about the pipe changed, so nobody thought to check it, and the new boiler underperforms from the first day. It then gets blamed on the appliance, the manufacturer, or the installer’s choice of model.

Other recurring causes:

  1. Appliances added over the years – a new hob, a gas fire, a second boiler – each seeming small, cumulatively exceeding the pipe’s capacity.
  2. A kitchen extension with a new range cooker on a supply that was at its limit.
  3. Long runs in larger properties, where the length itself dominates the drop.
  4. A boiler relocated further from the meter without upsizing the run.
  5. Microbore or undersized sections hidden in a run that is otherwise adequate.
  6. Old steel pipe with internal corrosion reducing the effective bore.

How the check is done

  1. Standing pressureAt the appliance, with nothing running. Establishes the baseline.
  2. Working pressure at the applianceWith the appliance running at full rate. The difference from standing is the drop caused by that appliance alone.
  3. Working pressure with everything runningEvery gas appliance in the property at full rate simultaneously. This is the condition the installation must satisfy and it is the test most often not done.
  4. Compare the drop against the permissible figureWithin it, the pipework is adequate. Beyond it, it is not.
  5. Check the gas rateBy timing the meter, to confirm the appliance is actually consuming what its data plate says. An appliance under-rating is not achieving its output.
  6. Check the meter’s capacitySeparately from the pipework. A meter has a maximum throughput and it is a different constraint.

The whole thing takes a few minutes with a manometer and it should be part of every boiler survey and every service. Its absence is one of the more informative things about a quote.

When the pipework is inadequate

Solution When it applies
Upsize the run from the meter Most common answer. Replace the undersized section with larger pipe
Upsize only the first section Sometimes sufficient – the drop is dominated by the smallest, longest section
Re-route to shorten the run Where a shorter route is available
Reduce fittings Fewer, swept bends rather than many tight ones
Separate runs to separate appliances Where one appliance is a long way from the rest
Upgrade the meter Where the meter itself is the limit. Arranged through the gas transporter, not by an installer
Choose a lower-output appliance Occasionally the honest answer, if upsizing is impractical

The meter point is worth understanding. Meter capacity is separate from pipe capacity, and increasing it is a matter for the gas transporter rather than a plumbing contractor. It takes time to arrange, and it is best discovered at survey rather than on installation day.

How pipework must be installed

  • Correct materials and jointing. Copper with appropriate fittings, or steel. Certain fittings permitted on water are not permitted on gas, and the distinction is not cosmetic.
  • Protection where the pipe could be damaged, and sleeving where it passes through walls.
  • Support at the correct intervals.
  • Ventilation of voids. Gas pipe must not run in an unventilated void where a leak could accumulate. Pipe in a sealed floor void or a boxed duct needs ventilation at both ends.
  • Cavity walls – generally pipe may only cross a cavity by the shortest direct route, not run within it.
  • Electrical bonding at the correct point near the meter, with an adequately sized conductor. Very commonly found missing or undersized on older installations, and routinely picked up at safety checks.
  • Tightness testing and purging on any new or altered installation, with results recorded.
  • Accessible isolation to each appliance.

What to ask

  1. Has the gas rate been checked against the data plate?
  2. Has working pressure been measured with every appliance running?
  3. What is the permissible drop and what did you measure?
  4. Is the existing pipework adequate for the new appliance?
  5. Is the meter capacity adequate?
  6. If upsizing is needed, is it in the quote?

These are not difficult questions and any competent installer will have the answers. A quote for a higher-output boiler on existing pipework, with no mention of the supply check, is a quote with a risk in it that has not been priced.

Fitting a higher-output boiler on old pipework? The supply check takes minutes and it prevents a problem nobody later associates with the pipe.

Call 07506 070316

Questions we get asked about this

How do I know if my gas pipe is big enough?

It is measured, not estimated – a working pressure test at the appliance with everything running, compared against the permissible drop. If that check was not done when a new boiler went in, it is worth having done.

My hob and boiler cannot both run properly.

That is the classic symptom of an undersized supply. The installation cannot deliver the combined demand within the permissible pressure drop. It is diagnosable in a single visit with a manometer.

Does a new boiler need a bigger gas pipe?

Sometimes. A modern appliance frequently has a higher output than the one it replaces, and the existing pipe was sized for the old one. It is a check, not an assumption, in either direction.

What if the meter is the constraint?

Meter capacity is separate from pipe capacity and upgrading it is arranged through the gas transporter rather than by an installer. It takes time, which is why it is much better found at survey.

Can gas pipe run under a floor?

Yes, with appropriate protection and with the void ventilated. A sealed, unventilated void is the problem, because a leak has nowhere to disperse to.

What is gas bonding and do I need it?

Main protective bonding connects the gas installation to the electrical earthing system at the correct point near the meter. It is a genuine safety requirement and it is frequently found missing or undersized on older installations.

Need this doing?

Call and describe the problem — you will speak to an engineer, not a call centre. Written quotes, no estimates over the phone.

Call now Get a quote