F-Gas: what the regulations actually cover, in plain English

What F-Gas covers, who it applies to, what the operator must do, and why most facilities managers do not know their obligations.

Short answer

The regulations cover fluorinated greenhouse gases used as refrigerants. They impose duties on the equipment operator around leak prevention, leak checking, record keeping, using certified people, and recovery at end of life.

What the regulations are for

Fluorinated greenhouse gases are used as refrigerants because they have excellent thermodynamic properties. They are also, molecule for molecule, extremely potent greenhouse gases – some thousands of times more so than carbon dioxide.

The regulatory response has two strands:

  1. Contain what is already installed. Prevent leaks, find them quickly when they occur, and recover refrigerant at end of life rather than letting it escape.
  2. Reduce what goes in in future. A phase-down quota progressively restricting the quantity of high-GWP refrigerant placed on the market, pushing the industry toward lower-GWP alternatives.

Everything in the regime follows from those two objectives, which makes the individual obligations easier to remember than a list of rules.

What equipment is covered

  • Air conditioning – splits, multi-splits, VRF, cassettes, ducted systems, close control.
  • Refrigeration – commercial cold rooms, display cabinets, cellar cooling, process refrigeration.
  • Heat pumps, including air source heat pumps.
  • Chillers.
  • Some fire protection systems and certain other applications.
  • Not systems using non-fluorinated refrigerants such as propane, ammonia or CO2 – though those have their own safety regimes.

The scope surprises people. Cellar cooling in a pub, display fridges in a shop, and a comms room split unit are all covered exactly as a VRF system is, and they are frequently overlooked because nobody thinks of them as ‘F-Gas equipment’.

Who the duty falls on

The regulations place obligations on the operator – defined as the person or business with actual control over the technical functioning of the equipment.

In practice that is normally the occupier or the building owner, not the maintenance contractor. The distinguishing question is who can decide whether the equipment runs, who pays for its maintenance, and who would decide to replace it.

The duty cannot be contracted away

You can and should appoint certified contractors to carry out the work. The legal responsibility for it happening, and for the records existing, stays with you. A regulator asking questions asks the operator – and ‘our contractor deals with that’ is not an answer that transfers the duty. See operator or contractor.

What the operator must do

Duty In practice
Prevent leaks Maintain the equipment properly, and repair leaks without undue delay
Leak checking At a frequency determined by the system’s CO2e, by a certified person
Repair and re-check A detected leak must be repaired, and the system re-checked within a defined period afterwards to confirm the repair worked
Automatic leak detection Required above a higher CO2e threshold, and the detection system itself must be checked periodically
Records Quantity and type installed, quantities added and recovered, who did the work, dates and results of checks, and end-of-life measures
Use certified personnel and companies Both are required – individual qualification and company certification
Recovery at end of life Refrigerant must be recovered by a certified person, with records
Labelling Equipment must be labelled with the refrigerant type and quantity

The one that trips people up is the re-check after repair. Repairing a leak is not the end of the obligation – the system must be verified afterwards within a defined period to confirm the repair was effective.

CO2e: the number everything hangs on

Almost every threshold in the regime is expressed in tonnes of CO2 equivalent, not in kilograms of refrigerant.

CO2e = refrigerant charge in kilograms x that refrigerant’s global warming potential.

The consequence is that two physically similar systems can have completely different obligations, because their refrigerants have very different GWPs. A system charged with a high-GWP refrigerant reaches a threshold at a much smaller physical quantity than one using a low-GWP alternative.

This is why the first practical step in any F-Gas compliance exercise is establishing, for every system, what refrigerant it contains and how much. Both are on the nameplate, and both should be in the commissioning records. Without them, nothing else can be calculated.

The thresholds and the resulting frequencies are worked through in leak check frequency.

Hermetically sealed equipment

A useful distinction worth knowing. Equipment described as hermetically sealed – where the refrigerant circuit is sealed by welding, brazing or a similar permanent joint, with no serviceable connections, and labelled as such – has a higher CO2e threshold before leak checking applies.

The logic is that a circuit with no serviceable joints has a much lower leak risk than one with flare connections and service valves. Many small self-contained units fall into this category.

Two cautions: the equipment must actually be labelled as hermetically sealed, and the higher threshold applies only to the leak checking obligation – the handling, certification, recovery and record obligations are unaffected.

What to do if you have never thought about this

  1. Find every systemAir conditioning, refrigeration, cellar cooling, comms room cooling, chillers, heat pumps. Walk the building, including the roof and anywhere plant might be hiding.
  2. Record refrigerant type and charge for eachFrom the nameplate. Photograph them.
  3. Calculate CO2e for eachCharge multiplied by GWP.
  4. Establish the resulting obligationsLeak check frequency, and whether automatic leak detection is required.
  5. Set up recordsA logbook per system, held by you as operator – not only by your contractor.
  6. Confirm your contractor’s certificationIndividual qualifications and company certification. Ask for evidence.
  7. Start the scheduleYou cannot recreate past checks. A site that is compliant going forward is in a very different position from one that still is not.

Not sure what you have? The asset survey and the CO2e calculation take one visit and produce an answer either way.

Call 07506 070316

Questions we get asked about this

Who is the operator under F-Gas?

The person or business with actual control over the technical functioning of the equipment – normally the occupier or owner, not the maintenance contractor. The duty cannot be transferred by contract.

Does F-Gas apply to small split systems?

The handling and certification requirements apply regardless of size. Mandatory periodic leak checking applies only above a CO2e threshold, which many small splits fall below.

Does it apply to refrigeration as well as air conditioning?

Yes. Cold rooms, display cabinets, cellar cooling and process refrigeration all count, and they are among the most commonly overlooked systems in a CO2e calculation.

What is CO2e?

Refrigerant charge in kilograms multiplied by the refrigerant’s global warming potential. It is the figure the regulatory thresholds are expressed in, and it determines your obligations.

What is hermetically sealed equipment?

Equipment where the refrigerant circuit is sealed permanently with no serviceable joints, and labelled as such. It has a higher threshold before leak checking applies, reflecting the lower leak risk.

What happens if we have never done any of this?

Start now. Survey the equipment, calculate CO2e, set the correct schedule and begin recording. You cannot recreate past checks, and demonstrating a competent regime going forward is a very different position from still not having one.