Burst pipe or no heating? We take emergency call-outs across Norfolk — 07506 070316

Commercial & larger works →
Lex Plumbing Call 07506 070316
Oil
Boilers
Tanks and supply
Gas
Boilers
Safety and appliances
Cooling
Air conditioning
Heat pumps
Hot water
Cylinders
Problems and parts
Heating
Systems
Controls and parts
Plumbing
Emergencies
Everyday plumbing
Mains and waste
Bathrooms
Installations
Fittings
GuidesAreasContact
F-Gas compliance

Leak check frequency: working out your CO2e and your schedule

How to calculate your system's CO2e, how it determines leak check frequency, and how automatic leak detection changes it.

Short answer

CO2e is refrigerant charge multiplied by GWP. Thresholds expressed in tonnes of CO2e determine whether leak checking is required and at what interval, with the interval shortening as CO2e rises and extending where automatic leak detection is fitted.

The calculation

CO2e (tonnes) = refrigerant charge (kg) x GWP / 1000

You need two figures, and both are on the outdoor unit’s nameplate:

  1. The refrigerant type – R410A, R32, R134a, R407C and so on.
  2. The charge quantity in kilograms.

The GWP for each refrigerant is published in the regulation and is a fixed figure. Multiply, divide by a thousand, and you have the system’s CO2e in tonnes.

Additional charge counts

The nameplate figure is usually the factory charge. Where pipe runs exceeded the pre-charged length, additional refrigerant was added at commissioning – and that counts towards the total. If your commissioning records show additional charge, add it. If nobody recorded it, that is a gap worth closing, because you cannot demonstrate compliance without an accurate total.

What the thresholds do

The regime works in bands. Below the lowest threshold there is no mandatory periodic leak checking at all. Above it, checking is required, and the interval shortens as CO2e rises through successive bands.

As CO2e rises What changes
Below the lowest threshold No mandatory periodic leak checking
Above the first threshold Periodic leak checking required
Above the next threshold More frequent checking required
Above the highest threshold More frequent checking again, plus a fixed automatic leak detection system
Hermetically sealed and labelled as such A higher threshold applies before checking is required at all
Automatic leak detection fitted The required interval is extended

We are deliberately describing the structure rather than quoting the specific figures and intervals, because they are set in regulation, they have changed, and a number remembered from a training course several years ago is exactly how people end up non-compliant. Check the current gov.uk guidance, or ask us to calculate it against the rules as they stand.

Worked through, conceptually

  1. Find the nameplateOn the outdoor unit. Photograph it – you will want this again.
  2. Note the refrigerant typeWritten as R followed by a number.
  3. Note the charge in kilogramsSometimes given in grams – check the units.
  4. Add any additional chargeFrom commissioning records, where pipe runs required it.
  5. Look up the GWPFor that refrigerant, from the current published values.
  6. Multiply and divide by 1000Giving tonnes of CO2e.
  7. Compare against the current thresholdsWhich gives you the required interval, or confirms no mandatory checking applies.
  8. Check whether automatic leak detection is requiredAnd whether fitting it voluntarily would extend your interval usefully.
  9. Record the resultPer system, in the logbook. This is the calculation an inspector would want to see.

Repeat for every system on the site. It is a short job per unit and it is the foundation of everything else.

Why identical-looking systems differ

This is the part that surprises people, and it is worth understanding because it affects replacement decisions.

Refrigerant GWPs vary by a large factor. A system charged with a high-GWP refrigerant reaches any given CO2e threshold at a much smaller physical quantity than a system using a lower-GWP one.

Practical consequences:

  • Two visually identical units with the same physical charge can fall either side of a threshold purely because of refrigerant type.
  • Replacing old plant with equivalent capacity on a modern low-GWP refrigerant can move a system below a threshold, reducing your ongoing compliance burden – which is a genuine and often unconsidered benefit of replacement.
  • A larger system on a low-GWP refrigerant may have fewer obligations than a smaller one on a high-GWP refrigerant.
  • Adding a system to a site does not aggregate – each system is assessed on its own CO2e, not the site total.

That last point matters. The threshold applies per system, not per site. Ten small splits each below the threshold have no mandatory leak checking; one VRF system with the same total charge may have quarterly checking.

Automatic leak detection

Above a defined CO2e threshold, a fixed automatic leak detection system is mandatory. Below it, fitting one voluntarily extends the permitted interval between manual checks.

Worth knowing:

  • It must alert the operator or a service company when a leak is detected – a detector that alarms locally in an empty plant room is of limited use.
  • The detection system itself must be checked at defined intervals to confirm it is functioning.
  • It does not remove the manual checking obligation, it extends the interval.
  • On borderline systems, fitting one voluntarily can be economically sensible, halving the number of manual check visits over the plant’s life. Worth doing the arithmetic.

What a leak check actually involves

It is not a visual inspection and it is not the same as a service.

  • Carried out by a certified person working for a certified company.
  • Using an appropriate method – a calibrated electronic leak detector, or an indirect method based on system parameters where the standards permit it.
  • Covering the parts most prone to leakage – joints, valves, seals, flares, service ports, and areas subject to vibration.
  • Recorded in the system logbook with the date, the method, the result and who carried it out.
  • Followed by repair without undue delay where a leak is found, and a re-check within the defined period afterwards to verify the repair.

A maintenance visit is not automatically a leak check, and a leak check is not a service. Both need to happen, both need recording, and conflating them is a common source of gaps – see what an F-Gas logbook must contain.

Have systems but no CO2e figures? One survey produces the register, the calculations and the resulting schedule.

Call 07506 070316

Questions we get asked about this

How do I calculate CO2e?

Refrigerant charge in kilograms multiplied by that refrigerant’s GWP, divided by 1000 to give tonnes. Both figures for the charge and type are on the outdoor unit nameplate.

How often do I need leak checks?

It depends on the system’s CO2e against the current thresholds. Below the lowest there is no mandatory checking; above it the interval shortens as CO2e rises. Check the current guidance rather than a remembered figure.

Does the threshold apply per system or per site?

Per system. Ten small splits each below the threshold have no mandatory checking; one large system with the same total charge may have frequent checking.

Does fitting leak detection reduce how often I need manual checks?

Yes – it extends the permitted interval, and above a higher threshold it becomes mandatory anyway. On borderline systems it can be economically worthwhile.

Is a service the same as a leak check?

No. They are separate obligations with separate records. A maintenance visit does not automatically constitute a leak check, and conflating them is a common source of compliance gaps.

What if additional refrigerant was added at installation?

It counts towards the total charge for CO2e purposes. If nobody recorded it, that is a gap worth closing – you cannot demonstrate compliance without an accurate charge figure.

Sources

Regulations and standards referenced on this page

Need this doing?

Call and describe the problem — you will speak to an engineer, not a call centre. Written quotes, no estimates over the phone.

Call now Get a quote