Burst pipe or no heating? We take emergency call-outs across Norfolk — 07506 070316

Commercial & larger works →
Lex Plumbing Call 07506 070316
Oil
Boilers
Tanks and supply
Gas
Boilers
Safety and appliances
Cooling
Air conditioning
Heat pumps
Hot water
Cylinders
Problems and parts
Heating
Systems
Controls and parts
Plumbing
Emergencies
Everyday plumbing
Mains and waste
Bathrooms
Installations
Fittings
GuidesAreasContact
Commercial air conditioning

VRF and VRV systems

VRF and VRV systems across East Anglia - multi-zone cooling and heating, heat recovery, and the F-Gas obligations that come with a large charge.

Short answer

VRF varies refrigerant flow to each indoor unit, allowing many zones on one system with individual control. Heat recovery versions can heat and cool simultaneously, moving heat from one zone to another. The large refrigerant charge brings F-Gas obligations that smaller systems do not have.

What VRF actually does

A conventional split system’s outdoor unit is either on or off, serving its indoor units at whatever capacity it is running. A VRF system varies the refrigerant flow to each indoor unit independently, so twelve indoor units can each run at a different capacity from a single outdoor unit, with the compressor modulating to match the total.

That gives you individual zone control at real part-load efficiency, which is the whole argument. A building where three rooms are occupied out of twenty runs a VRF system at low output rather than cycling a large system on and off.

Heat pump versus heat recovery

A heat pump VRF system runs all indoor units in the same mode – everything cooling, or everything heating. It is cheaper and it suits buildings whose zones genuinely all want the same thing.

A heat recovery VRF system runs some indoor units in cooling and others in heating at the same time, using branch controllers to route refrigerant appropriately. Critically, the heat extracted from the zones being cooled is delivered to the zones being heated rather than rejected outside. In a multi-aspect office in a British spring – south side overheating from solar gain, north side cold – that is genuinely efficient, not marketing.

The honest test of whether heat recovery is worth the premium: does your building actually have zones that want opposite things at the same time? If it is a single-aspect unit, it does not, and a heat pump system or even a multi-split is the better value.

Design considerations that matter later

  • Connected capacity ratio. Manufacturers specify the maximum total indoor capacity that may be connected to a given outdoor unit. Over-connecting relies on diversity being real, and it is not on the days everybody is in.
  • Pipe lengths and level differences. Every system specifies maximum total pipe length, maximum length to the furthest indoor unit, and maximum height difference. These are not soft limits – exceeding them degrades oil return, which damages compressors over time.
  • Branch controller positions must be accessible for maintenance. A branch controller above a fixed plasterboard ceiling is a problem waiting for a fault.
  • Condensate from every indoor unit. Gravity drainage wherever possible. A building with twenty condensate pumps in ceiling voids has twenty future leaks.
  • Refrigerant leak risk assessment. Refrigerant is heavier than air. In a small enclosed room served by a system with a large charge, a leak could displace oxygen, and the standards require the risk to be assessed and mitigated – typically with leak detection and ventilation.
  • Controls and BMS integration. Decide at design whether the system is standalone or integrating with a building management system, because retrofitting the interface is far more expensive.
The charge is large, and that has legal consequences

A VRF system contains far more refrigerant than a split, which means a much higher CO2e and therefore more frequent statutory leak checking, and often a requirement for automatic leak detection. This is a real ongoing obligation and cost, and it should be understood before the system is chosen rather than after – see F-Gas compliance.

Maintaining a VRF system

The maintenance regime has two separate strands and they are commonly confused.

Strand Driven by Typical frequency
Preventative maintenance Manufacturer requirements and duty One to two visits a year – filters, coils, drainage, electrical, controls
F-Gas leak checking Law, based on the system’s CO2e Set by the regulations – could be annual, six-monthly or three-monthly

A maintenance visit is not automatically a leak check, and a leak check is not a service. Both must happen, both must be recorded, and the F-Gas records must go in the system logbook – see what an F-Gas logbook must contain.

Beyond that, the specific things that matter on VRF: keeping every indoor unit’s filters clean, because one blocked unit affects the whole system’s balance; keeping condensate paths clear, because there are many of them; and monitoring operating pressures and superheat across the system rather than at one point, because a VRF system will mask a developing problem until it becomes a failure.

Common problems on existing systems

  • Refrigerant charge lost over time. Frequently from flare joints on the original installation. It shows as declining performance across the whole system rather than a single unit failing.
  • Over-connected outdoor units that were fine when the building was half occupied and are not now.
  • Branch controllers made inaccessible by subsequent ceiling works.
  • Controls nobody understands, with zones locked out or running on defaults set at commissioning years ago.
  • Condensate pump failures producing ceiling damage.
  • No records. No commissioning data, no charge figures, no logbook. This is a compliance problem as well as a maintenance one, and reconstructing it takes time.
  • Obsolete refrigerant, which as the phase-down progresses makes a repair progressively harder to justify – see the refrigerant phase-down.

Inherited a VRF system with no records? The asset survey is the first job, and it establishes both what you have and what you are obliged to do.

Call 07506 070316

Questions we get asked about this

What is the difference between VRF and VRV?

Technically nothing – VRV is one manufacturer’s trade name and VRF is the generic term for the same technology. They are used interchangeably.

Do we need heat recovery or is heat pump enough?

Heat recovery is worth the premium only if your building genuinely has zones wanting opposite things at the same time – typically a multi-aspect building with significant solar gain on one side. A single-aspect unit does not need it.

How many indoor units can one system serve?

It depends on the outdoor unit’s capacity and the manufacturer’s connected-capacity limits – commonly a substantial number, which is the point of VRF. The practical limits are usually pipe length and building routes rather than unit count.

What are our F-Gas obligations with a VRF system?

Leak checking at a frequency set by the system’s CO2e, records kept in a logbook, work carried out only by qualified people working for a certified company, and automatic leak detection above a threshold charge. See the F-Gas compliance page.

Can VRF heat the building in winter?

Yes, and efficiently. A heat recovery system in particular moves heat from zones that need cooling to zones that need heating, which is considerably better than generating it.

Can we extend the system later?

Only within the outdoor unit’s connected capacity and the pipework limits, and only if it was designed with that headroom. Retrofitting additional indoor units onto a fully loaded system is not possible – say at design stage if expansion is likely.

Regulations and standards referenced on this page

How it works

What happens when you call

01

Call and describe it

You speak to an engineer, not a call centre. Most jobs can be narrowed down on the phone.

02

We look at it properly

A real diagnosis before a price, and a straight answer if it is not worth doing.

03

A written quote

Itemised, so you can see what you are paying for.

04

The job, and the paperwork

Certificates where the work needs them, and what will need attention next.

Coverage

Where we do this work

Across Norwich and the whole of Norfolk. If you are on the edge of the county, call and ask — we will tell you honestly whether we are the right people.

  • Norwich
  • Wymondham
  • Dereham
  • Attleborough
  • Aylsham
  • North Walsham
  • Cromer
  • Diss
  • Loddon
  • Long Stratton
  • Watton
  • King's Lynn

All areas we cover →

Need this doing?

Call and describe the problem — you will speak to an engineer, not a call centre. Written quotes, no estimates over the phone.

Call now Get a quote